11 KV VCB Panels (indoor/Outdoor)
Advance Medium Voltage Switchboards , HT Panels are free standing, Floor mounting with separate chambers for VCB, Bus Bar, CT / PT Cable Chamber & Metering – Protection Relays Compartments covering wide range from 3.3 kV to 33 kV offering as alliance partner with Schneider Electric. VCB’s are supplied by Schneider Electric.
Manufactured under strict guideline in fully integrated manufacturing and testing facilities, every product is subject to compliance with national and international standard and reach the customers as the ultimate proof of protection, performance and cutting-edge technology.
We provide complete solution for scattered application of medium voltage switch gears panels in compliance to IEC – 62271-200.
Technical Features
|
Sr. No.
|
Description
|
MV Switchboards
|
11 kV - VCB Panels
|
1
|
Construction
|
Modular & Rigid, Both side Expandable Type
|
2
|
Application
|
Indoor/ Outdoor / Kiosk Design
|
3
|
Mounting
|
Floor Mounting
|
4
|
IP Class
|
IP 4X / 54 ( Indoor) IP 55 ( Outdoor)
|
5
|
Busbar Design
|
Copper & Aluminium Both
|
6
|
Reference Standard
|
IEC 62271-200 / IS:3427:1997
|
7
|
Rated Current
|
800A/1250A/1600A/2000A/2500A/3150A
|
8
|
Rated Frequency
|
50/60Hz
|
9
|
Rated Short Time Withstand Current
|
20kA,25kA, 26.3kA,31.5kA, 40 kA
|
10
|
Rated Voltage
|
3.3 kV/ 6.6 kV / 11 kV
|
11
|
Power Frequency Withstand Voltage
|
28kV
|
12
|
Control Voltage
|
24V/30V/110V/230V AC/DC Potential Free contacts available for remote monitoring & operations
|
13
|
Control & Monitoring
|
Any communication protocol through relays / pot free aux. contacts.
|
14
|
Features
|
Test, Service & Isolated positions indications inside.
|
Withdrawable assembly & metal enclosed, No Direct access to live parts. Live parts covered by automatic shutters when VCB is racked out.
|
Horizontal draw out with Easy VCB interchangeability in similar rating. VCB are tested to withstand Internal Arc Fault.
|
VCB Operating Mechanism is manual & motorized spring charged .
|
Removable Fuses are mounted on PT .
|
Robust & virtually Maintenance Free Design
|
Separate Earthing Truck Available as optional (Cable & Bus Side )
|
Breaker Handling Trolley Optional
|
Mechanical Counter Optional
|
Operationally safe & reliable in a wide range of ambient temperature
|
Both Electrical & Mechanical safety interlocks are provided
|
3.3 KV /6.6 kV Panels are supplied with 11 KV VCB with PT of 3.3 KV & 6.6 kV
|
15
|
Cable Entry
|
Top / Bottom Both
|
16
|
Access
|
Single Front
|
Products Range
|
Sr. No.
|
Description
|
1
|
Standard Indoor / Outdoor AIS ( VCB) Cubical with ICOG / Switchboard Configuration
|
2
|
Flexible and customized CICO /Bus-duct / Top bushing design to suite all customer need
|
3
|
Available in fixed and as well as draw out version
|
4
|
Type tested incompliance to IEC 62271-200
|
Get in Touch